We have designed a PID control loop simulator using Matlab and Simulink. Below is the PID control loop graphically designed using Simulink (Matlab and Simulink are excellent software design tools developed by The MathWorks Inc). The PID controller we have implemented is of type C. For more info about different types of PID controller please visit http://bestune.50megs.com/typeABC.htm.
The PID controller contains a built in digital filter. It receives 8 inputs:
x(1): Filtered PV, which will be further filtered in the built in digital filter.
x(2): Setpoint.
x(3): The proportional gain Kp.
x(4): The integral gain Ki.
x(5): The derivative gain Kd.
x(6): Time.
x(7): If it is 1, then use PID control action, otherwise use manual CO value.
x(8): Manual CO value.
The PID controller plus a built in digital filter is designed as a Matlab function "pid1.m", as shown below.
function u=pid(x)
global Tpid Tf t0 t1 tf k
global sp ek uk uk_1 yk yk_1 vk vk_1
t=x(6); % Read time
if t==0
k=0;
Tpid=1; % PID loop update time
t0=0;
t1=0;
uk=x(8); % Initial CO value
yk=x(1); % Initial PV value
sp=x(2); % Initial setpoint
ek=sp-yk;
Tf=0.1; % Filter time constant
tf=200; % Simulation stop time
else % Filtering yk
T0=t-t0;
yk=yk*Tf/(Tf+T0)+x(1)*T0/(Tf+T0);
t0=t;
end
if t-t1>=Tpid | x(2)~=sp %Every Tpid sec calculate the new CO value
sp=x(2);
T=t-t1;
if T>0.0001 %Avoid division by T=0
if x(7)==1 & k>=3 % Then use PID control
Kp=x(3);
Ki=x(4);
Kd=x(5);
ek=sp-yk;
vk=(yk-yk_1)/T;
ak=(vk-vk_1)/T;
Du=(Ki*ek-Kp*vk-Kd*ak)*T;
uk=uk_1+Du;
else
if k>=1 vk=(yk-yk_1)/T; end
if k>=2 ak=(vk-vk_1)/T; end
uk=x(8); % Use manual uk value x(8)
k=k+1;
end
end
if uk>5 uk=5;end % uk must be <= upper limit
if uk<-5 uk=-5;end % uk must be >= lower limit
% Show the control results and update t1, yk_1, vk_1, uk_1
fprintf('time=%5.2f setpoint=%5.2f pv=%5.2f co=%5.2f\n',t,x(2),yk,uk)
t1=t;yk_1=yk;vk_1=vk;uk_1=uk;
end
% End of the PID controller
u=uk;
The filter part is scaned at a very high frequency (i.e., every T0 seconds the filter will be executed once and T0 is very small). The PID controller is executed every Tpid=1 seconds.
Please note that the filter design and PID controller design are separated. When you tune this PID controller, the filter should be considered as a part of the process. So strictly speaking each time when you make changes to the filter, you should re-tune your PID parameters.